POWER SYSTEM ANALYSIS
SEM-VI, 2012
B.TECH EXAMINATION
UTTARAKHAND TECHNICAL UNIVERSITY
(UTU)
Time :3 hours
Total
Marks:100
Note: Attempt all
questions
Attempt any four parts
out of the following
- Why do we prefer to analyze unsymmetrical faults by
symmetrical component methods?
- A single phase two-winding transformer is rated 20 kVA,
480/120 V, 60 Hz. The equivalent leakage impedance of the transformer referred
to the 120V winding 2, is Zeq2 = 0.0525 ∠ 78.13oΩ.
Using transformer ratings as base values determine the per unit leakage
impedance referred to winding 2 and referred to winding 1.
- Bus voltages at Bus-1 and Bus-2 in a two-bus system
with a purely reactive transmission line between Bus-1 and Bus-2 are 1.00∠ 0o
and 1.05∠ -10o ,respectively. In what directions real and
reactive powers will flow? Explain why?
- Transmission line between Bus-1 and Bus-2 of a two bus
system has a serial impedance of R + JX and shunt admittance of jY.
Find the Bus Admittance Matrix.
- What is the need of a reference buses are there in an
interconnected system?
Attempt any four parts
out of the following
- Define the following terms:
(i) Surge Impedance
(ii) Power System Stability
(iii) Symmetrical Components
(iv) One Line Diagram
(v) Reactance Diagram - What is difference between load bus and voltage control
bus?
- What are the steps used to find Ybus matrix?
- What are the advantages and disadvantages of Fast
Decoupled method of load-flow analysis?
- Write the swing equation describing the rotor dynamics
of a synchronous machine connected to infinite bus through a transmission
line. Explain the meaning of symbols used in the equation.
Attempt any two parts
out of the following
- Tap-setting of a 20 kVA, 50 Hz 2000/200 V transformer
on primary side is 90%. If its leakage reactance is 5Ω, draw the π-equivalent
circuit of this transformer and determine its bus admittance matrix. Use
p.u system. Neglect winding resistance, core losses, and magnetizing
reactance.
- A three phase 20 MVA, 10 kV alternator has internal
reactance of 5% and negligible resistance. Find the external reactance per
phase to be connected in series with the alternator so that steady current
on short circuit does not exceed 8 times the full load current.
- Derive an expression for fault current for single line
to ground fault by symmetrical components method.
Attempt any two parts
out of the following
- In a two-bus system with a slack bus (Bus-1) and a load
bus (Bus-2), voltage at Bus-1 is 1.00∠ 0o pu and power demand at
Bus-2 is (0.01 + j 0.01) pu. No generator is connected at Bus-2 and
no load is connected at Bus-1. Transmission line between Bus-1 and Bus-2
is lossless (and shunt-capacitance is also neglected) and has a series
reactance of 0.1 p.u.
(i) Use analytical method (direct calculations) to find the voltage at Bus-2 and power being generated by the generator at Bus-1.
(ii) Show the calculations for one iteration of Newton-Raphson method after assuming suitable initial guess. - Mention two objectives of short circuit analysis. Draw
the zero sequence network of a star connected generator with zero sequence
impedance Zgo when the neutral is grounded through an impedance
Zn.
- Derive the formula for fault current, fault-bus
voltages and current through the lines for a 3 phase symmetrical fault at
a bus in a power system using Zbus. State the assumptions made
in the derivation.
Attempt any two parts
out of the following
- A 11.2 kV, 10 MVA synchronous generator having a
sub-transient reactance of 0.25 p.u supplies 4 MW at 0.8 pf leading to a
11.2 kV, 5 MVA synchronous motor having a sub-transient reactance of 0.2
p.u. through a line having a reactance of 0.2 p.u. through a line having a
reactance of 0.05 p.u. The motor terminal voltage is 11.15 kV. Calculate
the total fault current supplied by the generator and the motor when a
three-phase dead short circuit occurs at generator terminals. Neglect all
losses.
- With a neat flow chart, explain the computational
procedure for load flow solution using Newton-Raphson iterative method
when the system contains all types of buses.
- Assume a (0.8 + j0.4) per unit load at bus 2 is being supplied by a generator at bus 1 through transmission line with series impedance of (0.05 + j0.1) per unit. Assuming bus 1 is the swing bus with a fixed per unit voltage of 1.0∠0o, use the Gauss-Seidel method to calculate the voltage at bus 2 after 1 iteration.
______________utu previous year question papers of B.tech, Bba, B.com, B.sc and Mba old year question papers Uttarakhand technical University (UTU)________________-
No comments:
Post a Comment